Siemens AG SIMATIC S7-1200, SIMATIC S7-1500

CVE-2018-13815
HIGH 7.5

En bref

Source
NVD
EPSS
EPSS 1.80 % · centile 78 ()
État
PUBLISHED
Publiée
Mise à jour
Attribuée par
siemens
Statut NVD
Modified

Description

A vulnerability has been identified in SIMATIC S7-1200 (All versions), SIMATIC S7-1500 (All Versions < V2.6). An attacker could exhaust the available connection pool of an affected device by opening a sufficient number of connections to the device. Successful exploitation requires an attacker to be able to send packets to port 102/tcp of the affected device. No user interaction and no user privileges are required to exploit the vulnerability. The vulnerability, if exploited, could cause a Denial-of-Service condition impacting the availability of the system. At the time of advisory publication no public exploitation of this vulnerability was known.

Faiblesses (CWE)

  • CWE-410 — Insufficient Resource Pool
  • CWE-400 — Consommation de ressources non maîtrisée (déni de service)

Références

Scores

VersionScoreVecteurÉvalué par
CVSS 3.0HIGH 7.5CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:HNVD · nvd@nist.gov (Primary)
CVSS 2.0MEDIUM 5.0AV:N/AC:L/Au:N/C:N/I:N/A:PNVD · nvd@nist.gov (Primary)

Références européennes

Avis du CERT-FR

Configurations affectées (CPE NVD)

Produits affectés

ProduitVersions
Siemens AG · SIMATIC S7-1200, SIMATIC S7-1500affected SIMATIC S7-1200 : All versions ; affected SIMATIC S7-1500 : All Versions < V2.6

Sources

SourceLicence
CVE List (CVEProject cvelistV5)CVE Program Terms of Use
EPSS (FIRST.org)FIRST — attribution requested
ENISA EUVDENISA — reproduction authorised, source acknowledged
CERT-FR (ANSSI)Licence Ouverte / Etalab 2.0
NVD (NIST) via fkie-cad/nvd-json-data-feedsPublic domain — this product uses data from the NVD API but is not endorsed or certified by the NVD