Siemens AG SIMATIC PCS 7 V8.0 and earlier

CVE-2019-10935
HIGH 7.2

At a glance

Source
NVD
EPSS
EPSS 1.27 % · percentile 70 ()
State
PUBLISHED
Published
Updated
Assigner
siemens
NVD status
Modified

Description

A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd 11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC Professional (TIA Portal V13) (All versions), SIMATIC WinCC Professional (TIA Portal V14) (All versions < V14 SP1 Upd 9), SIMATIC WinCC Professional (TIA Portal V15) (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). The SIMATIC WinCC DataMonitor web application of the affected products allows to upload arbitrary ASPX code. The security vulnerability could be exploited by an authenticated attacker with network access to the WinCC DataMonitor application. No user interaction is required to exploit this vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the affected device. At the stage of publishing this security advisory no public exploitation is known.

Weaknesses (CWE)

  • CWE-434 — Unrestricted Upload of File with Dangerous Type

References

Scores

VersionScoreVectorScored by
CVSS 3.0HIGH 7.2CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:HNVD · nvd@nist.gov (Primary)
CVSS 2.0MEDIUM 6.5AV:N/AC:L/Au:S/C:P/I:P/A:PNVD · nvd@nist.gov (Primary)

European references

CERT-FR advisories

Affected configurations (NVD CPE)

Affected products

ProductVersions
Siemens AG · SIMATIC PCS 7 V8.0 and earlieraffected All versions
Siemens AG · SIMATIC PCS 7 V8.1affected All versions < V8.1 with WinCC V7.3 Upd 19
Siemens AG · SIMATIC PCS 7 V8.2affected All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd 11
Siemens AG · SIMATIC PCS 7 V9.0affected All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11
Siemens AG · SIMATIC WinCC Professional (TIA Portal V13)affected All versions
Siemens AG · SIMATIC WinCC Professional (TIA Portal V14)affected All versions < V14 SP1 Upd 9
Siemens AG · SIMATIC WinCC Professional (TIA Portal V15)affected All versions < V15.1 Upd 3
Siemens AG · SIMATIC WinCC Runtime Professional V13affected All versions
Siemens AG · SIMATIC WinCC Runtime Professional V14affected All versions < V14.1 Upd 8
Siemens AG · SIMATIC WinCC Runtime Professional V15affected All versions < V15.1 Upd 3
Siemens AG · SIMATIC WinCC V7.2 and earlieraffected All versions
Siemens AG · SIMATIC WinCC V7.3affected All versions < V7.3 Upd 19
Siemens AG · SIMATIC WinCC V7.4affected All versions < V7.4 SP1 Upd 11
Siemens AG · SIMATIC WinCC V7.5affected All versions < V7.5 Upd 3

Sources

SourceLicence
CVE List (CVEProject cvelistV5)CVE Program Terms of Use
EPSS (FIRST.org)FIRST — attribution requested
ENISA EUVDENISA — reproduction authorised, source acknowledged
CERT-FR (ANSSI)Licence Ouverte / Etalab 2.0
NVD (NIST) via fkie-cad/nvd-json-data-feedsPublic domain — this product uses data from the NVD API but is not endorsed or certified by the NVD