Siemens AG SIMATIC HMI Comfort Panels 4" - 22"
En bref
- Source
- NVD
- EPSS
- EPSS 2.72 % · centile 86 ()
- État
- PUBLISHED
- Publiée
- Mise à jour
- Attribuée par
- siemens
- Statut NVD
- Modified
Description
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1 Update 1), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Professional (All versions < V15.1 Update 1), SIMATIC WinCC (TIA Portal) (All versions < V15.1 Update 1), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The affected device offered SNMP read and write capacities with a publicly know hardcoded community string. The security vulnerability could be exploited by an attacker with network access to the affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.
Faiblesses (CWE)
- CWE-200 — Exposition d'informations sensibles à un acteur non autorisé
- CWE-798 — Utilisation d'identifiants codés en dur
Références
Scores
| Version | Score | Vecteur | Évalué par |
|---|---|---|---|
| CVSS 3.1 | CRITICAL 9.1 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N | NVD · nvd@nist.gov (Primary) |
| CVSS 2.0 | MEDIUM 6.4 | AV:N/AC:L/Au:N/C:P/I:P/A:N | NVD · nvd@nist.gov (Primary) |
Références européennes
- ENISA EUVD · EUVD-2019-16131
- GCVE · GCVE-0-2019-6572
Avis du CERT-FR
- CERTFR-2019-AVI-207 — Multiples vulnérabilités dans les produits Siemens · cert.ssi.gouv.fr
Configurations affectées (CPE NVD)
cpe:2.3:o:siemens:simatic_hmi_comfort_panels_firmware:*:*:*:*:*:*:*:*< 15.1cpe:2.3:o:siemens:simatic_hmi_comfort_outdoor_panels_firmware:*:*:*:*:*:*:*:*< 15.1cpe:2.3:o:siemens:simatic_hmi_ktp_mobile_panels_ktp400f_firmware:*:*:*:*:*:*:*:*< 15.1cpe:2.3:o:siemens:simatic_hmi_ktp_mobile_panels_ktp700_firmware:*:*:*:*:*:*:*:*< 15.1cpe:2.3:o:siemens:simatic_hmi_ktp_mobile_panels_ktp700f_firmware:*:*:*:*:*:*:*:*< 15.1cpe:2.3:o:siemens:simatic_hmi_ktp_mobile_panels_ktp900_firmware:*:*:*:*:*:*:*:*< 15.1cpe:2.3:o:siemens:simatic_hmi_ktp_mobile_panels_ktp900f_firmware:*:*:*:*:*:*:*:*< 15.1cpe:2.3:a:siemens:simatic_wincc_\(tia_portal\):*:*:*:*:*:*:*:*< 15.1cpe:2.3:a:siemens:simatic_wincc_runtime:*:*:*:*:advanced:*:*:*< 15.1cpe:2.3:a:siemens:simatic_wincc_runtime:*:*:*:*:professional:*:*:*< 15.1cpe:2.3:o:siemens:simatic_hmi_tp_firmware:*:*:*:*:*:*:*:*cpe:2.3:o:siemens:simatic_hmi_mp_firmware:*:*:*:*:*:*:*:*cpe:2.3:o:siemens:simatic_hmi_op_firmware:*:*:*:*:*:*:*:*
Produits affectés
| Produit | Versions |
|---|---|
| Siemens AG · SIMATIC HMI Comfort Panels 4" - 22" | affected All versions < V15.1 Update 1 |
| Siemens AG · SIMATIC HMI Comfort Outdoor Panels 7" & 15" | affected All versions < V15.1 Update 1 |
| Siemens AG · SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F | affected All versions < V15.1 Update 1 |
| Siemens AG · SIMATIC WinCC Runtime Advanced | affected All versions < V15.1 Update 1 |
| Siemens AG · SIMATIC WinCC Runtime Professional | affected All versions < V15.1 Update 1 |
| Siemens AG · SIMATIC WinCC (TIA Portal) | affected All versions < V15.1 Update 1 |
| Siemens AG · SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) | affected All versions |
Sources
| Source | Licence |
|---|---|
| CVE List (CVEProject cvelistV5) | CVE Program Terms of Use |
| EPSS (FIRST.org) | FIRST — attribution requested |
| ENISA EUVD | ENISA — reproduction authorised, source acknowledged |
| CERT-FR (ANSSI) | Licence Ouverte / Etalab 2.0 |
| NVD (NIST) via fkie-cad/nvd-json-data-feeds | Public domain — this product uses data from the NVD API but is not endorsed or certified by the NVD |