Rockwell Automation ISaGRAF5 Runtime Relative Path Traversal (Rockwell Automation ISaGRAF Runtime)
En bref
- Source
- NVD
- EPSS
- EPSS 6.42 % · centile 94 ()
- État
- PUBLISHED
- Publiée
- Mise à jour
- Attribuée par
- icscert
- Statut NVD
- Modified
Description
Some commands used by the Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x eXchange Layer (IXL) protocol perform various file operations in the file system. Since the parameter pointing to the file name is not checked for reserved characters, it is possible for a remote, unauthenticated attacker to traverse an application’s directory, which could lead to remote code execution.
Faiblesses (CWE)
Références
- https://www.cisa.gov/uscert/ics/advisories/icsa-20-280-01
- https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1131699
- https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-159-04
- https://www.xylem.com/siteassets/about-xylem/cybersecurity/advisories/xylem-multismart-rockwell-isagraf.pdf
Scores
| Version | Score | Vecteur | Évalué par |
|---|---|---|---|
| CVSS 3.1 | CRITICAL 9.1 | CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H | icscert |
| CVSS 3.1 | CRITICAL 9.1 | CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:C/C:H/I:H/A:H | NVD · ics-cert@hq.dhs.gov (Secondary) |
| CVSS 3.1 | CRITICAL 9.8 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H | NVD · nvd@nist.gov (Primary) |
| CVSS 2.0 | HIGH 9.3 | AV:N/AC:M/Au:N/C:C/I:C/A:C | NVD · nvd@nist.gov (Primary) |
Références européennes
- ENISA EUVD · EUVD-2020-17867
- GCVE · GCVE-0-2020-25176
Avis du CERT-FR
- CERTFR-2024-AVI-0013 — Multiples vulnérabilités dans les produits Schneider Electric · cert.ssi.gouv.fr
- CERTFR-2021-AVI-911 — Multiples vulnérabilités dans Moxa ioPAC · cert.ssi.gouv.fr
- CERTFR-2021-AVI-443 — Multiples vulnérabilités dans les produits Schneider Electric · cert.ssi.gouv.fr
Configurations affectées (CPE NVD)
cpe:2.3:o:schneider-electric:easergy_t300_firmware:*:*:*:*:*:*:*:*≤ 2.7.1cpe:2.3:o:schneider-electric:easergy_c5_firmware:*:*:*:*:*:*:*:*< 1.1.0cpe:2.3:o:schneider-electric:micom_c264_firmware:*:*:*:*:*:*:*:*< d6.1cpe:2.3:o:schneider-electric:pacis_gtw_firmware:5.1:*:*:*:*:windows:*:*cpe:2.3:o:schneider-electric:pacis_gtw_firmware:5.2:*:*:*:*:windows:*:*cpe:2.3:o:schneider-electric:pacis_gtw_firmware:6.1:*:*:*:*:windows:*:*cpe:2.3:o:schneider-electric:pacis_gtw_firmware:6.3:*:*:*:*:linux:*:*cpe:2.3:o:schneider-electric:pacis_gtw_firmware:6.3:*:*:*:*:windows:*:*cpe:2.3:o:schneider-electric:saitel_dp_firmware:*:*:*:*:*:*:*:*≤ 11.06.21cpe:2.3:o:schneider-electric:epas_gtw_firmware:6.4:*:*:*:*:linux:*:*cpe:2.3:o:schneider-electric:epas_gtw_firmware:6.4:*:*:*:*:windows:*:*cpe:2.3:o:schneider-electric:saitel_dr_firmware:*:*:*:*:*:*:*:*≤ 11.06.12cpe:2.3:o:schneider-electric:scd2200_firmware:*:*:*:*:*:*:*:*≤ 10024cpe:2.3:a:rockwellautomation:aadvance_controller:*:*:*:*:*:*:*:*≤ 1.40cpe:2.3:a:rockwellautomation:isagraf_free_runtime:*:*:*:*:*:isagraf6_workbench:*:*≤ 6.6.8cpe:2.3:a:rockwellautomation:isagraf_runtime:*:*:*:*:*:*:*:*≥ 5.0 < 6.0cpe:2.3:o:rockwellautomation:micro810_firmware:-:*:*:*:*:*:*:*cpe:2.3:o:rockwellautomation:micro820_firmware:-:*:*:*:*:*:*:*cpe:2.3:o:rockwellautomation:micro830_firmware:-:*:*:*:*:*:*:*cpe:2.3:o:rockwellautomation:micro850_firmware:-:*:*:*:*:*:*:*cpe:2.3:o:rockwellautomation:micro870_firmware:-:*:*:*:*:*:*:*cpe:2.3:o:xylem:multismart_firmware:*:*:*:*:*:*:*:*< 3.2.0
Produits affectés
| Produit | Versions |
|---|---|
| Rockwell Automation · ISaGRAF Runtime | affected 4.x ; affected 5.x |
Sources
| Source | Licence |
|---|---|
| CVE List (CVEProject cvelistV5) | CVE Program Terms of Use |
| EPSS (FIRST.org) | FIRST — attribution requested |
| ENISA EUVD | ENISA — reproduction authorised, source acknowledged |
| CERT-FR (ANSSI) | Licence Ouverte / Etalab 2.0 |
| NVD (NIST) via fkie-cad/nvd-json-data-feeds | Public domain — this product uses data from the NVD API but is not endorsed or certified by the NVD |