Rockwell Automation ISaGRAF5 Runtime Unprotected Storage of Credentials (Rockwell Automation ISaGRAF Runtime)
En bref
- Source
- NVD
- EPSS
- EPSS 0.44 % · centile 38 ()
- État
- PUBLISHED
- Publiée
- Mise à jour
- Attribuée par
- icscert
- Statut NVD
- Modified
Rechercher sur…
Description
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x stores the password in plaintext in a file that is in the same directory as the executable file. ISaGRAF Runtime reads the file and saves the data in a variable without any additional modification. A local, unauthenticated attacker could compromise the user passwords, resulting in information disclosure.
Faiblesses (CWE)
Références
- https://www.cisa.gov/uscert/ics/advisories/icsa-20-280-01
- https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1131699
- https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-159-04
- https://www.xylem.com/siteassets/about-xylem/cybersecurity/advisories/xylem-multismart-rockwell-isagraf.pdf
Scores
| Version | Score | Vecteur | Évalué par |
|---|---|---|---|
| CVSS 3.1 | HIGH 7.8 | CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H | icscert |
| CVSS 3.1 | HIGH 7.8 | CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H | NVD · ics-cert@hq.dhs.gov (Secondary) |
| CVSS 3.1 | MEDIUM 5.5 | CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N | NVD · nvd@nist.gov (Primary) |
| CVSS 2.0 | LOW 2.1 | AV:L/AC:L/Au:N/C:P/I:N/A:N | NVD · nvd@nist.gov (Primary) |
Références européennes
- ENISA EUVD · EUVD-2020-17875
- GCVE · GCVE-0-2020-25184
Avis du CERT-FR
- CERTFR-2024-AVI-0013 — Multiples vulnérabilités dans les produits Schneider Electric · cert.ssi.gouv.fr
- CERTFR-2021-AVI-911 — Multiples vulnérabilités dans Moxa ioPAC · cert.ssi.gouv.fr
- CERTFR-2021-AVI-443 — Multiples vulnérabilités dans les produits Schneider Electric · cert.ssi.gouv.fr
Configurations affectées (CPE NVD)
cpe:2.3:o:schneider-electric:easergy_t300_firmware:*:*:*:*:*:*:*:*≤ 2.7.1cpe:2.3:o:schneider-electric:easergy_c5_firmware:*:*:*:*:*:*:*:*< 1.1.0cpe:2.3:o:schneider-electric:micom_c264_firmware:*:*:*:*:*:*:*:*< d6.1cpe:2.3:o:schneider-electric:pacis_gtw_firmware:5.1:*:*:*:*:windows:*:*cpe:2.3:o:schneider-electric:pacis_gtw_firmware:5.2:*:*:*:*:windows:*:*cpe:2.3:o:schneider-electric:pacis_gtw_firmware:6.1:*:*:*:*:windows:*:*cpe:2.3:o:schneider-electric:pacis_gtw_firmware:6.3:*:*:*:*:linux:*:*cpe:2.3:o:schneider-electric:pacis_gtw_firmware:6.3:*:*:*:*:windows:*:*cpe:2.3:o:schneider-electric:saitel_dp_firmware:*:*:*:*:*:*:*:*≤ 11.06.21cpe:2.3:o:schneider-electric:epas_gtw_firmware:6.4:*:*:*:*:linux:*:*cpe:2.3:o:schneider-electric:epas_gtw_firmware:6.4:*:*:*:*:windows:*:*cpe:2.3:o:schneider-electric:saitel_dr_firmware:*:*:*:*:*:*:*:*≤ 11.06.12cpe:2.3:o:schneider-electric:scd2200_firmware:*:*:*:*:*:*:*:*≤ 10024cpe:2.3:a:rockwellautomation:aadvance_controller:*:*:*:*:*:*:*:*≤ 1.40cpe:2.3:a:rockwellautomation:isagraf_free_runtime:*:*:*:*:*:isagraf6_workbench:*:*≤ 6.6.8cpe:2.3:a:rockwellautomation:isagraf_runtime:*:*:*:*:*:*:*:*≥ 5.0 < 6.0cpe:2.3:o:rockwellautomation:micro810_firmware:-:*:*:*:*:*:*:*cpe:2.3:o:rockwellautomation:micro820_firmware:-:*:*:*:*:*:*:*cpe:2.3:o:rockwellautomation:micro830_firmware:-:*:*:*:*:*:*:*cpe:2.3:o:rockwellautomation:micro850_firmware:-:*:*:*:*:*:*:*cpe:2.3:o:rockwellautomation:micro870_firmware:-:*:*:*:*:*:*:*cpe:2.3:o:xylem:multismart_firmware:*:*:*:*:*:*:*:*< 3.2.0
Produits affectés
| Produit | Versions |
|---|---|
| Rockwell Automation · ISaGRAF Runtime | affected 4.x ; affected 5.x |
Sources
| Source | Licence |
|---|---|
| CVE List (CVEProject cvelistV5) | CVE Program Terms of Use |
| EPSS (FIRST.org) | FIRST — attribution requested |
| ENISA EUVD | ENISA — reproduction authorised, source acknowledged |
| CERT-FR (ANSSI) | Licence Ouverte / Etalab 2.0 |
| NVD (NIST) via fkie-cad/nvd-json-data-feeds | Public domain — this product uses data from the NVD API but is not endorsed or certified by the NVD |